Ry U (1 ) BK RLS EMG Ry C 24V 24V 0V 0V M 24V (2 ) BK RLS Ry EMG C 24V 24V 0V M 24V 0V (3 ) BK RLS Ry EMG C 24V 24V 0V M 24V 0V OFF 21 - 3() DC24V M24V EMG () DC24V 0V Ry Ry U (1 ) BK RLS EMG C 24V Ry 24V 0V M 24V 0V (2 ) BK RLS EMG C 24V Ry 24V 0V M 24V 0V (3 ) BK RLS EMG C 24V Ry 24V 0V M 24V 0V DC24V M24V EMG M24V(SETUP ON) (M24V) M24VBK RLS 22 - 6.
(Circuit example) The figure below shows the stopped state. 24 VDC 0V Reset switch for stop Ry stop switch Surge suppressor Ry U Power supply plug (The 1st driver) BK RLS EMG C 24V Ry 24V 0V Driver M 24V Power supply 0V Power supply plug (The 2nd driver) BK RLS EMG C 24V Ry 24V 0V Driver M 24V Power supply 0V Power supply plug (The 3rd driver) BK RLS EMG C 24V Ry 24V 0V Driver M 24V Power
(Circuit example: The figure below shows the stopped state.) 24 VDC 0V Reset switch for stop Ry stop switch Surge suppressor Ry U Power supply plug (the 1st controller) LK RLS (6) Ry (3) EMG (2) M 24V Controller power supply (1) C 24V 0V (4) 24VDC 0V Power supply plug (the 2nd controller) LK RLS (6) Ry (3) EMG (2) M 24V Controller power supply (1) C 24V 0V (4) 24VDC 0V Power supply plug (
(Circuit example: The figure below shows the stopped state.) 24 VDC 0V Reset switch for stop Ry stop switch Ry Surge suppressor Power supply plug (the 1st controller) BK RLS Ry EMG C 24V Controller 24V M 24V power supply 0V 0V Power supply plug (the 2nd controller) BK RLS Ry EMG C 24V Controller 24V M 24V power supply 0V 0V Power supply plug (the 3rd controller) BK RLS Ry EMG C 24V Controller
RWr RWw RX RY RWr RWw Station I15..
(Circuit example) 0V 24VDC The stop is released switch Ry Stop Switch Surge suppressor Ry: Relay U Power supply plug 1 LK RLS (6) Ry (3) EMG (2) M 24V Controller (1) C 24V 0V (4) Input power supply DC24V 0V Power supply plug 2 LK RLS (6) Ry (3) EMG (2) M 24V Controller (1) C 24V 0V (4) Input power supply DC24V 0V Power supply plug 3 LK RLS (6) Ry (3) EMG (2) M 24V Controller (1) C 24V 0V
U Ry LK RLS6 Ry (1 ) (3) EMG (2) M 24V (1) C 24V 0V4 DC24V 0V LK RLS6 Ry (2 ) (3)EMG (2)M 24V (1)C 24V 0V4 DC24V 0V LK RLS(6) Ry 3 (3)EMG (2)M 24V (1)C 24V 0V(4) DC24V 0V OFF 28 - 32 DC24V M24V EMG () 0V DC24V Ry (1 ) (3)EMG LK RLS6 Ry (1)C 24V (2)M 24V 0V4 DC24V 0V (2 ) (3)EMG LK RLS6 Ry (1)C 24V (2)M 24V 0V4 DC24V 0V (3 ) (3)EMG LK RLS6 Ry (1)C 24V (2)M 24V 0V4 DC24V
Ry: U LK RLS (6) Ry (1 ) (3) EMG (2) M 24V (1) C 24V 0V (4) DC24V 0V LK RLS (6) Ry (2 ) (3) EMG (2) M 24V (1) C 24V 0V (4) DC24V 0V LK RLS (6) Ry (3 ) (3) EMG (2) M 24V (1) C 24V 0V (4) DC24V 0V OFF -28- (3)((2)) DC24V M24V EMG () 0V DC24V Ry (1 ) (3) EMG LK RLS (6) Ry (1) C 24V (2) M 24V 0V (4) DC24V 0V (2 ) (3) EMG LK RLS (6) Ry (1) C 24V (2) M 24V 0V (4) DC24V 0V (3 )
Bit area Input (RX) Output (RY) RDX EXW1-RDX* (16 points) 16 0 RDY EXW1-RDY* (16 points) 0 16 Compact wireless Remote RDM EXW1-RDM* (8 points) 16*1 16*1 *1: The number of inputs/outputs is fixed at 16 (16 bits), and only the lower 8 bits are valid. -72No.EX-OMZ0016-C EX600-W Series Unit name Model Unit product no.
For Long Stroke Bore size (mm) 40 Stroke range (mm) RT RY 501 to 800 RY 601 to 1000 50 76 30 1001 to 1200 601 to 1000 63 1001 to 1200 92 40 751 to 1000 80 RT 1001 to 1400 112 45 751 to 1000 100 1001 to 1500 136 50 Stroke range (mm) A Bore size (mm) 40 50 63 80 100 B B1 C AL D E F G H1 J K KA LD LH LS LT Without rod boot With rod boot 60 9.0 up to 500 20 to 500 30 27 22 44 16 32
RY RT (mm) Stroke range (mm) A Bore size (mm) 40 50 63 80 100 AL B B1 C D E F G H1 J K KA LD LH LS LT With rod boot Without rod boot 20 to 800 Up to 800 30 27 60 22 44 16 32 10 15 8 M8 x 1.25 6 14 9.0 40 138 3.2 Up to 1200 20 to 1200 35 32 70 27 52 20 40 10 17 11 M8 x 1.25 7 18 9.0 45 144 3.2 Up to 1200 20 to 1200 35 32 85 27 64 20 40 10 17 11 M10 x 1.25 7 18 11.5 50 166 3.2 20 to 1400 Up
(Circuit example) * The figure below shows the stopped state. 0V 24VDC Reset switch for stop Ry stop switch Ry Surge suppressor Power supply plug (the 1st controller) RG+ RG0V M 24V C 24V EMG BK RLS Ry Controller power supply 24V 0V Power supply plug (the 2nd controller) RG+ RG0V M 24V C 24V EMG BK RLS Ry Controller power supply 24V 0V Power supply plug (the 3rd controller) 0V M 24V C 24V
LEC6 DC24 0V Shutdown is lifted Switch Ry Stop Switch Gateway EMG + Surge suppressor Ry Unit EMG Power supply plug (1st. unit) BK RLS EMG Ry C 24V Controller input power 24V 0V 0V M 24V Power supply plug (2nd. unit) BK RLS EMG Ry C 24V Controller input power 24V 0V 0V M 24V Power supply plug (3rd. unit) BK RLS EMG Ry C 24V Controller input power 24V 0V 0V M 24V Caution When the stop signal
CN4 CN2 EMG+ EMG24V 0V (CN2SW)ON EMG+,EMG-(LEC)OFF (LEC)(EMG+,EMG-) 22 - (LEC) ()LEC6 DC24V 0V Ry EMG+ Ry EMG(1 ) BK RLS EMG Ry C 24V 24V M 24V 0V 0V (2 ) BK RLS EMG Ry C 24V 24V M 24V 0V 0V (3 ) BK RLS EMG Ry C 24V 24V M 24V 0V 0V (LEC)OFF 23 - 7.CN3 1 1 DA CC-Link A 2 2 DB CC-Link B 3 3 DG CC-Link 4 4 SLD CC-Link 5 5 FG CC-Link CC-Link CC-Link 1105%, 1/2W CC-Link
LEC6 DC24 0V Shutdown is lifted Switch Ry Stop Switch Gateway EMG + Surge suppressor Ry Unit EMG Power supply plug (1st. unit) BK RLS EMG Ry C 24V Controller input power 24V 0V 0V M 24V Power supply plug (2nd. unit) BK RLS EMG Ry C 24V Controller input power 24V 0V 0V M 24V Power supply plug (3rd. unit) BK RLS EMG Ry C 24V Controller input power 24V 0V 0V M 24V Caution When the stop signal
CN2TB/PC () 19 - .CN4 6.1 1 EMG+ EMG 2 EMGEMG 3 24V 5 4 3 2 () 4 0V 5 FG FG (LEC)(0V) ULUL1310Class2 6.2 2) AWG20(0.5mm (24V0V) 60 2) EMG AWG20(0.5mm (EMG+,EMG-) 60 8mm 20 - D(100) D 6.3 (CN2SW)ON(EMG+,EMG-) (LEC)EMG (CN2SW) RY CN4 CN2 EMG+ EMG24V 0V (CN2SW)ON EMG+,EMG-(LEC) OFF (LEC)(EMG+,EMG-) 21 - (LEC) ( LEC6) DC24V 0V Ry EMG+ Ry EMG(1) BK RLS EMG Ry C 24V 24V
LEC6 DC24 0V Shutdown is lifted Switch Ry Stop Switch Gateway EMG + Surge suppressor Ry Unit EMG Power supply plug (1st. unit) BK RLS EMG Ry C 24V Controller input power 24V 0V 0V M 24V Power supply plug (2nd. unit) BK RLS EMG Ry C 24V Controller input power 24V 0V 0V M 24V Power supply plug (3rd. unit) BK RLS EMG Ry C 24V Controller input power 24V 0V 0V M 24V Caution When the stop signal
CN4 CN2 EMG+ EMG24V 0V CN2SW EMG+,EMG-(LEC) (LEC)EMG+,EMG-OPEN 24 - (LEC) LEC6 (DC24V 0V ) Ry EMG+ Ry EMG(1 ) BK RLS EMG Ry C 24V 24V M 24V 0V 0V (2 ) BK RLS EMG Ry C 24V 24V M 24V 0V 0V (3 ) BK RLS EMG Ry C 24V 24V M 24V 0V 0V LECOFF 25 - 7CN3: 1 5 4 3 2 1 2 5 4 3 2 1 9 8 7 6 9 8 7 6 3 RXDTXD-P / 4 5 DGND 6 VP 7 8 RXD/TXD-N / 9 PRODIBUS DP 6GK1 500
LEC6 DC24 0V Shutdown is lifted Switch Ry Stop Switch Gateway EMG + Surge suppressor Ry Unit EMG Power supply plug (1st. unit) BK RLS EMG Ry C 24V Controller input power 24V 0V 0V M 24V Power supply plug (2nd. unit) BK RLS EMG Ry C 24V Controller input power 24V 0V 0V M 24V Power supply plug (3rd. unit) BK RLS EMG Ry C 24V Controller input power 24V 0V 0V M 24V Caution When the stop signal
EMG+,EMGEMG+,EMGCN4 EMG+ 0V EMGRy Ry Ry: BK RLS LEC 1 LEC 1 EMG Ry C 24V LEC LEC 24V M 24V 0V 0V BK RLS LEC 2 LEC 1 EMG Ry C 24V LEC LEC 24V M 24V 0V 0V LEC 3 BK RLS LEC 1 EMG Ry C 24V LEC LEC 24V M 24V 0V 0V 30 - GW GW (CN2SW)ON GW (CN2SW)OFF (CN4)EMG+EMGLEC (EMG+,EMG-OPEN) LEC OFF 7.CN1(CONT) 7.1 GW 12 LEC GW CONT (CN1)LEC 5.LEC-CAP-X22 3.