SMC Corporation of America
Elite Part Number Search
Search Results "HRSH090-A-40-M"

AFD20-A) and NPT1/4 (applicable to the AFM30-A/40-A, AFD30-A/40-A).

-W-m (Water-cooled refrigeration) HRSH090-A-m (Air-cooled refrigeration) * This circuit construction of the position of the parts may be different from actual product.

20 30 40 Sensitivity current mA 30 Rated operating current*4 A 8.5 15 19 Rated power consumption*4 kW (kVA) 5.6 (5.9) 9.4 (10.2) 12.3 (13.0) Noise level (Front 1 m/Height 1 m)*4 dB (A) 75 75 71 Accessories Operation Manual (for installation/operation) 2 pcs.

DIN rail holding screw (For DIN rail mounting) VM 4(A) port side: Blue (For rubber seal) : Gray (For metal seal) 2(B) port side: Yellow (Light/surge voltage suppressor) XT34 (DIN rail) (8) B A B A B A B A B A (35) 14 A 14 A 14 A 14 A A 14 39.6 64.4 128.8 3.9 82.7 115 (5.5) 5.5 96.7 (77.1) B 12 B 12 B 12 B 12 12 B 0.6 m, 1.5 m, 3 m (Lead wire length) 8.8 (6) (9.3) 18 (17.9) (A, B port: 12)

Filter Rc1/2 20 m V V 3 Valve Rc1 V Rc1/2 V 4 Valve Rc1/2 V V 9 Y-strainer Rc3/8 #40 V V Install either the strainer or filter. If foreign matter with a size of 20 m or more are likely to enter, select the particle filter, and then prepare it. Filter Rc3/8 20 m V V 5 Flow meter Rc1 V Prepare a flow meter with an appropriate flow range.

40 A 4 cores x 8 mm2 (4 cores x AWG8) (Including grounding cable) R8-5 HRSH250--20 50 A 4 cores x 8 mm2 (4 cores x AWG8) (Including grounding cable) R8-5 M5 A HRSH100--40 20 A 3 x 5.5 mm2 (3 x AWG10) (Power supply) 1 x 14 mm2 (1 x AWG6) (Grounding cable) R5.5-5 (Power supply) R14-5 (Grounding cable) HRSH150--40 HRSH200--40 HRSH250--40 3-phase 380 to 415 VAC (50/60 Hz) 30 A Note) An example

30 40 Sensitivity of leak current mA 30 Rated operating current 50/60 Hz Note 5) A 14/15 16/19 Rated power consumption 50/60 Hz Note 5) kW (kVA) 3.8/4.8 (4.9/5.3) 4.7/6.1 (5.6/6.7) Noise level (Front 1 m/Height 1 m) Note 5) dB (A) 70 70 Waterproof specification IPX4 Accessories Alarm code list stickers 2 pcs.

30 40 Sensitivity of leak current mA 30 Rated operating current 50/60 Hz Note 5) A 13/14 16/19 Rated power consumption 50/60 Hz Note 5) kW 3.4/4.4 (4.4/5.0) 4.6/6.0 (5.6/6.6) Noise level (Front 1 m/Height 1 m) Note 5) dB (A) 70 70 Waterproof specication IPX4 Accessories Alarm code list stickers 2 pcs.

20. 9-1 9.1.2 HRS090-A-40. 9-2 9.1.3 HRS090-A-46. 9-3 9.1.4 HRS090-W-20. 9-4 9.1.5 HRS090-W-40. 9-5 9.1.6 HRS090-W-46. 9-6 9.1.7 Refrigerant with GWP reference . 9-7 9.1.8 Communication specification . 9-7 9.2 Outline dimensions . 9-8 9.2.1 HRS090-A-20/40/46-. 9-8 9.2.2 HRS090-W-20/40/46-. 9-9 9.3 Flow diagram . 9-10 9.3.1 HRS090-A-20/40/46-. 9-10 9.3.2 HRS090-W-20/40/46 . 9-10 9.4 Cooling

fluid temperature [C] Pump Capacity HRS090-A-20/40 HRS090-W-20/40 0.5 50 Usable range (50 Hz) Circulating fluid pressure [MPa] Circulating fluid outlet (60 Hz) 0.4 40 Pump head [m] 0.3 30 Circulating fluid outlet (50 Hz) 0.2 20 Usable range (60 Hz) 0.1 10 Circulating fluid return port 0 0 0 10 20 30 40 50 60 70 Circulating fluid flow rate [L/min] 78 Thermo-chiller Standard Type HRS090 Series

For installation indoors, ventilation ports and a ventilation fan should be equipped as needed. 300 mm or more 500 mm or more 100 mm or more Altitude [m] q Upper limit of ambient temperature [C] w Cooling capacity coefficient Power supply 100 V type Power supply 200/230 V type Less than 1000 m 35 40 1.00 Less than 1500 m 34 38 0.85 Less than 2000 m 33 36 0.80 Less than 2500 m 32 34 0.75 Less

Cooling Method: A (Air-cooled Refrigeration), Pipe Thread: F (G, w/Rc-G Conversion Fitting), Power Supply: 40 (3-phase 380 to 415 VAC, 50/60 Hz; 3-phase 460 to 480 VAC (60 Hz)), Option: M (Applicable to Deionized Water Piping)

Cooling Method: A (Air-cooled Refrigeration), Pipe Thread: N (NPT, w/Rc-NPT Conversion Fitting), Power Supply: 40 (3-phase 380 to 415 VAC, 50/60 Hz; 3-phase 460 to 480 VAC (60 Hz)), Option: M (Applicable to Deionized Water Piping)

Cooling Method: W (Water-cooled Refrigeration), Pipe Thread: F (G, w/Rc-G Conversion Fitting), Power Supply: 40 (3-phase 380 to 415 VAC, 50/60 Hz; 3-phase 460 to 480 VAC (60 Hz)), Option: M (Applicable to Deionized Water Piping)

Cooling Method: Air-cooled Refrigeration, Pipe Thread: G, w/Rc-G Conversion Fitting, Power Supply: 3-phase 380 to 415 VAC, 50/60 Hz; 3-phase 460 to 480 VAC (60 Hz), Option: Applicable to Deionized Water Piping