SMC Corporation of America
Elite Part Number Search
Search Results "HRS090-AN-20-J"

Cooling Method: A (Air-cooled Refrigeration), Pipe Thread: N [NPT (w/Rc-NPT Conversion Fitting)], Power Supply: 20 [3-phase 200 VAC (50 Hz); 3-phase 200 to 230 VAC (50/60 Hz], Option: JM (J + M)

Cooling Method: Air-cooled Refrigeration, Pipe Thread: N [NPT (w/Rc-NPT Conversion Fitting)], Power Supply: 20 [3-phase 200 VAC (50 Hz); 3-phase 200 to 230 VAC (50/60 Hz], Option: J + M

An angled supply port facilitates the supply of circulating fluid, even when units are stacked.  A large digital display provides a clear view of the current and set values. 

Contents Applicable model HRS-EP020 NPT thread conversion fitting set HRS090-A-20/40-J HRS-EP021 G thread conversion fitting set Part no.

Cooling Capacity HRL100-Am-20 (CH1)1 HRL200-Am-20 (CH1)1 14 30 12 Technical Data HRS-R HRS HRS090 HRS 100/150 HRS200 HRSH090 HRSH HRSE HRR HRL HRZ HRZD HRW HECR HEC HED HEB 25 Ambient temperature 32C Ambient temperature 32C Cooling capacity [kW] Cooling capacity [kW] 10 20 8 15 6 10 Ambient temperature 45C 4 Ambient temperature 45C 5 2 0 0 15 20 25 15 20 25 Circulating fluid temperature [

Applicable model HRS-WL003 HRS090-mm-20/40 Parts List q No.

Filter Rc3/8 20 m V V 5 Flow meter Rc1 V Prepare a flow meter with an appropriate flow range.

W: 13 [kW] W Efficiency Power supply output VI: 20 [kVA] Q = P = Q = P = V x I x Power factor In this example, using an efficiency of 0.7: In this example, using a power factor of 0.85: 13 0.7 = = 18.6 [kW] = 20 [kVA] x 0.85 = 17 [kW] Cooling capacity = Considering a safety factor of 20%, Cooling capacity = Considering a safety factor of 20%, 18.6 [kW] x 1.2 = 22.3 [kW] 17 [kW] x 1.2 = 20.4

415 VAC (50/60 Hz) 20 A M5 4 cores x 5.5 mm2 (4 cores x AWG10) (Including grounding cable R5.5-5) R5.5-5 HRS150-Al-40-l HRS150-Wl-40-l Note) An example of the cable specifications is when two kinds of vinyl insulated wires with a continuous allowable operating temperature of 70C at 600 V, are used at an ambient temperature of 30C.

20 [dm3] : 4.2 x 103 [J/(kgK)] : 305 [K] (32 [C]) : 293 [K] (20 [C]) : 12 [K] (= T0 Tt) : 900 [s] (= 15 [min]) Example of current measurement units (Reference) : Unknown [cal/h] [W] : Water : (= r x V) [kgf] : 1 [kgf/L] : 20 [L] : 1.0 x 103 [cal/(kgfC)] Heat quantity by cooled substance (per unit time) Q Cooled substance Cooled substance weight m Cooled substance weight volume ratio c

Table 2.4-20 List of set values Set value Explanation Initial value (Default setting) Sets LOCAL mode. Sets DIO mode. Sets SERIAL mode. HRS090 Series 2.4 Setting and checking 2-15 HRX-OM-T004 Chapter 2 Contact input/output communication 2.5 Contact input signal There are two contact input signals.

Cooling Method: A (Air-cooled Refrigeration), Pipe Thread: N [NPT (w/Rc-NPT Conversion Fitting)], Power Supply: 20 [3-phase 200 VAC (50 Hz); 3-phase 200 to 230 VAC (50/60 Hz]

Cooling Method: Air-cooled Refrigeration, Pipe Thread: N [NPT (w/Rc-NPT Conversion Fitting)], Power Supply: 20 [3-phase 200 VAC (50 Hz); 3-phase 200 to 230 VAC (50/60 Hz], Option: -

Cooling Method: A (Air-cooled Refrigeration), Pipe Thread: N [NPT (w/Rc-NPT Conversion Fitting)], Power Supply: 40 [3-phase 380 to 415 VAC (50/60 Hz)], Option: J (w/Automatic Fluid Fill Function)

Cooling Method: A (Air-cooled Refrigeration), Pipe Thread: N [NPT (w/Rc-NPT Conversion Fitting)], Power Supply: 46 [3-phase 380 to 415 VAC (50/60 Hz); 3-phase 460 to 480 VAC (60 Hz)], Option: J (w/Automatic Fluid Fill Function)