Your search for HRS returned 21 result(s)
There were no hits with the full part number, but there were 12 hits in the keyword search.
There were no hits with the full part number, but there were 10 hits in the keyword search.
Product Information » New Products Search Results
Cooling Method: A (Air-cooled Refrigeration), Pipe Thread: N [NPT (w/Rc-NPT Conversion Fitting)], Power Supply: 20 [3-phase 200 VAC (50 Hz); 3-phase 200 to 230 VAC (50/60 Hz], Option: JM (J + M)
Cooling Method: Air-cooled Refrigeration, Pipe Thread: N [NPT (w/Rc-NPT Conversion Fitting)], Power Supply: 20 [3-phase 200 VAC (50 Hz); 3-phase 200 to 230 VAC (50/60 Hz], Option: J + M
An angled supply port facilitates the supply of circulating fluid, even when units are stacked. A large digital display provides a clear view of the current and set values.
Contents Applicable model HRS-EP020 NPT thread conversion fitting set HRS090-A-20/40-J HRS-EP021 G thread conversion fitting set Part no.
Cooling Capacity HRL100-Am-20 (CH1)1 HRL200-Am-20 (CH1)1 14 30 12 Technical Data HRS-R HRS HRS090 HRS 100/150 HRS200 HRSH090 HRSH HRSE HRR HRL HRZ HRZD HRW HECR HEC HED HEB 25 Ambient temperature 32C Ambient temperature 32C Cooling capacity [kW] Cooling capacity [kW] 10 20 8 15 6 10 Ambient temperature 45C 4 Ambient temperature 45C 5 2 0 0 15 20 25 15 20 25 Circulating fluid temperature [
Applicable model HRS-WL003 HRS090-mm-20/40 Parts List q No.
Filter Rc3/8 20 m V V 5 Flow meter Rc1 V Prepare a flow meter with an appropriate flow range.
W: 13 [kW] W Efficiency Power supply output VI: 20 [kVA] Q = P = Q = P = V x I x Power factor In this example, using an efficiency of 0.7: In this example, using a power factor of 0.85: 13 0.7 = = 18.6 [kW] = 20 [kVA] x 0.85 = 17 [kW] Cooling capacity = Considering a safety factor of 20%, Cooling capacity = Considering a safety factor of 20%, 18.6 [kW] x 1.2 = 22.3 [kW] 17 [kW] x 1.2 = 20.4
415 VAC (50/60 Hz) 20 A M5 4 cores x 5.5 mm2 (4 cores x AWG10) (Including grounding cable R5.5-5) R5.5-5 HRS150-Al-40-l HRS150-Wl-40-l Note) An example of the cable specifications is when two kinds of vinyl insulated wires with a continuous allowable operating temperature of 70C at 600 V, are used at an ambient temperature of 30C.
20 [dm3] : 4.2 x 103 [J/(kgK)] : 305 [K] (32 [C]) : 293 [K] (20 [C]) : 12 [K] (= T0 Tt) : 900 [s] (= 15 [min]) Example of current measurement units (Reference) : Unknown [cal/h] [W] : Water : (= r x V) [kgf] : 1 [kgf/L] : 20 [L] : 1.0 x 103 [cal/(kgfC)] Heat quantity by cooled substance (per unit time) Q Cooled substance Cooled substance weight m Cooled substance weight volume ratio c
Table 2.4-20 List of set values Set value Explanation Initial value (Default setting) Sets LOCAL mode. Sets DIO mode. Sets SERIAL mode. HRS090 Series 2.4 Setting and checking 2-15 HRX-OM-T004 Chapter 2 Contact input/output communication 2.5 Contact input signal There are two contact input signals.
Cooling Method: A (Air-cooled Refrigeration), Pipe Thread: N [NPT (w/Rc-NPT Conversion Fitting)], Power Supply: 20 [3-phase 200 VAC (50 Hz); 3-phase 200 to 230 VAC (50/60 Hz]
Cooling Method: Air-cooled Refrigeration, Pipe Thread: N [NPT (w/Rc-NPT Conversion Fitting)], Power Supply: 20 [3-phase 200 VAC (50 Hz); 3-phase 200 to 230 VAC (50/60 Hz], Option: -
Cooling Method: A (Air-cooled Refrigeration), Pipe Thread: N [NPT (w/Rc-NPT Conversion Fitting)], Power Supply: 40 [3-phase 380 to 415 VAC (50/60 Hz)], Option: J (w/Automatic Fluid Fill Function)
Cooling Method: A (Air-cooled Refrigeration), Pipe Thread: N [NPT (w/Rc-NPT Conversion Fitting)], Power Supply: 46 [3-phase 380 to 415 VAC (50/60 Hz); 3-phase 460 to 480 VAC (60 Hz)], Option: J (w/Automatic Fluid Fill Function)