SMC Corporation of America
Elite Part Number Search
Search Results "HRS018-AN-20-M"

Cooling Capacity: 018 (Cooling Capacity: 1700/1900W, 50/60 Hz), Cooling Method: A (Air-cooled Refrigeration), Thread: N (NPT w/PT-NPT Conversion Fitting Set), Option: MT (M + T)

Type: -, Cooling Method: -, Cooling Capacity: 1,700/1,900 W (50/60 Hz), Piping thread type: NPT (PT-NPT conversion fitting set included), Optional specifications: Compatible with deionized water (pure water) piping / High pump head specification

An angled supply port facilitates the supply of circulating fluid, even when units are stacked. A large digital display provides a clear view of the current and set values.

This product is obsolete. Please contact us for the latest version.sales@ocaire.com, THERMO CHILLER (PROPRTY JDSU), OTHERS, HRS THERMO-CHILLERS, 2X, HRS - NO SIZE RATING, 94.79877 lb, ModelCooling capacity (W)Cooling methodPower supplyInternational standardsHRS0181700/1900 (50/60 Hz)Air-cooled refrigeration Water-cooled refrigerationSingle-phase 100 VAC (50/60 Hz), 115 VAC (60 Hz)

An angled supply port facilitates the supply of circulating fluid, even when units are stacked.  A large digital display provides a clear view of the current and set values. 

Terminal block for signal 4 x 20 7122 20 7001 75 94 107 752 Drain tube (O.D. 10, Length approx. 2 m) (Can also be connected on the other side.)

HRS012--20,HRS018--20, HRS024--20 . 9-11 9.6 Pump capacity . 9-12 9.6.1 HRS012--10-(BJM), HRS018--10-(BJM) . 9-12 9.6.2 HRS012--20-(BGJM), HRS018--20-(BGJM), HRS024--20-(BGJM) . 9-12 9.6.3 HRS012--10-T, HRS018--10-T, HRS012--10-MT, HRS018--10-MT . 9-13 9.6.4 HRS012--20-T, HRS018--20-T, HRS024--20-T . 9-13 9.6.5 HRS012--20-MT, HRS018--20-MT, HRS024--20-MT . 9-14 9.7 Required facility water

fluid pressure [Mpa] 20 Outlet60Hz 0.2 Pump head [m] 10 0.1 Outlet50Hz Return port 0.0 0 10 20 30 Circulating fluid flow [L/min] Fig 9.6-1 Pump capacity(HRS018/030--20-R) 9.6.2 HRS018-A-20-T-R, HRS030-A-20-T-R 0.8 80 0.7 70 available area Circulating fluid pressure [MPa] 0.6 60 Pump head[m] 0.5 50 Outlet: 60Hz 0.4 40 0.3 30 Outlet: 50Hz 0.2 20 available area 0.1 10 Return port 0.0 0 0 5

Model HRS018-A-20--R HRS030-A-20--R Cooling method Air-cooled refrigeration Refrigerant R410A (HFC) Refrigerant charge [kg] 0.39 Control method PID control Ambient temperature/Humidity/Altitude1 [C] Temperature: 5 to 45C, Humidity: 30 to 70%, Altitude: less than 3000 m Circulating fluid2 Tap water, 15% ethylene glycol aqueous solution4 Set temperature range1 [C] 5 to 40 Cooling capacity3

Note 9) Purchase an earth leakage breaker with current sensitivity of 15 mA or 30 mA separately. (A product with an optional earth leakage breaker (option B) is also available.)

Cooling Capacity: 018 (Cooling Capacity: 1700/1900W, 50/60 Hz), Cooling Method: A (Air-cooled Refrigeration), Thread: N (NPT w/PT-NPT Conversion Fitting Set)

Type: -, Cooling Method: -, Cooling Capacity: 1,700/1,900 W (50/60 Hz), Piping thread type: NPT (PT-NPT conversion fitting set included), Optional specifications: None

Cooling Capacity: 018 (Cooling Capacity: 1500/1700W, 50/60 Hz), Cooling Method: A (Air-cooled Refrigeration), Thread: N (NPT w/PT-NPT Conversion Fitting Set), Option: M [Applicable to DI Water (Deionized Water) Piping]

Cooling Capacity: Cooling Capacity: 1500/1700W, 50/60 Hz, Cooling Method: Air-cooled Refrigeration, Thread: NPT w/PT-NPT Conversion Fitting Set, Option: M [Applicable to DI Water (Deionized Water) Piping]

Cooling Capacity: 018 [Cooling Capacity: 1700/1900 W (50/60 Hz)], Pipe Thread: N (NPT with PT-NPT Conversion Fitting Set), Option: None