AR10-A AR20-A to 40-06-A t e t e q IN OUT IN OUT r r q w w Component Parts No.

9.6.3 HRS012--10-T, HRS018--10-T, HRS012--10-MT, HRS018-10-MT 0.8 80 0.7 70 Circulating fluid pressure [MPa] 0.6 60 0.5 Pump head [m] Available area 50 0.4 Outlet60Hz 40 0.3 30 Outlet50Hz 0.2 20 Return port 0.1 10 Available area 0.0 0 0 5 10 15 20 25 5 Circulating fluid flow [L/min] Fig 9.6-3 Pump capacity(HRS012--10-T, HRS018--10-T, HRS012--10-MT, HRS018--10-MT) 9.6.4 HRS012--20-T, HRS018

HRS012/018--10-T/MT HRS012/018/024/030--20-T HRS012/018/024/030--20-MTNote 1) Applicable model Rated flow50/60Hz Note 2) 3) 7(0.36MPa)/10(0.42MPa) 10(0.44MPa)/14(0.40MPa) 10(0.32MPa/)/14(0.32MPa) Pump 18/22 Maximum flow rate (50/60 Hz) L/min Maximum pump head (50/60 Hz) m 55 70 60 Output W 320 550 Circuit protector 15A (10 A for standard) A 15 Recommended earth leakage breaker capacity 15

Applicable model HRR012/018--10-T/MT*1 HRR012/018/024/030--20-T HRR012/018/024/030--20-MT1 Pump Rated flow (50/60 Hz)2, 3 L/min 7 (0.36 MPa)/10 (0.42 MPa) 10 (0.42 MPa)/14 (0.40 MPa) 10 (0.32 MPa)/14 (0.32 MPa) Maximum pump head (50/60 Hz) m 50 50 50 Output W 350 550 Circuit protector A 15 15 (10 A for standard) Recommended earth leakage breaker capacity A 15 Cooling capacity4 W The cooling

x V x C x iT it m x C x (T0 Tt) it Q = = 1 x 150 x 4.186 x 103 x 10 900 = = 6977 [J/s] 7.0 [kW] m x C x (T0 Tt) it x 860 x V x 60 x C x iT it x 860 Q = = Cooling capacity = Considering a safety factor of 20%, 7.0 [kW] x 1.2 = 1 x 150 x 60 x 1.0 x 103 x 10 15 x 860 8.4 [kW] = Q x t: Heat capacity [kJ] Thermo-chiller Water bath 6977 [W] = 7.0 [kW] 20C Cooling capacity = Considering a safety

air outlet 40 or less 330 10 954 715 1538 A 1026 4 x 12 984 627 677 Anchor bolt mounting position (View A) For piping port sizes, refer to the Parts Description on page 5. 2 HRL Series Dual Channel Refrigerated Thermo-chiller for Lasers Dimensions HRL200-A-40 Ventilation air inlet Ventilation air inlet Ventilation air outlet 715 40 or less 954 330 10 1538 A 1026 984 4 x 12 627 677 Anchor

As a guide, it should be replaced after 6000 to 8000 hours of operation.
For the HRS012/018/024/030 option “T” (high-pressure pump) and the HRS050/060, after 8000 hours, alarm code “AL28” (pump maintenance) will be activated.
We recommend that you check for leaks and replace the mechanical seal at this time. Consider requesting maintenance from a maintenance company.

This is a legacy product. Please contact us for the latest version.sales@ocaire.com, MAIN PC BOARD / HRS012-W-20-T, OTHERS, HRS THERMO-CHILLERS, 21, HRS - NO SIZE RATING, .00000 lb

filter to be done easily and without tools.Compact type thermal-chiller , Single phase, 100/115VAC, Cooling method: air-cooled or water-cooled , Self diagnosis and check display for easy maintenance , Functions: timer operation, low tank level detecting, power failure auto-restart, anti-freezing, PC BOARD / HRS012-A-10, OTHERS, HRS THERMO-CHILLERS, 21, HRS - NO SIZE RATING, .00000 lb

A large digital display provides a clear view of the current and set values.

This is a legacy product. Please contact us for the latest version.sales@ocaire.com, PC BOARD / HRS012-W-10, OTHERS, HRS THERMO-CHILLERS, 21, HRS - NO SIZE RATING, .00000 lb

Cooling Capacity: 012 (Cooling Capacity: 1100/1300W, 50/60 Hz), Cooling Method: A (Air-cooled Refrigeration), Thread: F (G w/PT-G Conversion Fitting Set), Option: T (High-pressure Pump)

Cooling Capacity: 012 (Cooling Capacity: 1100/1300W, 50/60 Hz), Cooling Method: W (Water-cooled Refrigeration), Thread: N (NPT w/PT-NPT Conversion Fitting Set), Option: T (High-pressure Pump)