SMC Corporation of America
Elite Part Number Search
Search Results "HRSH200-AN-20-BKW"
An angled supply port facilitates the supply of circulating fluid, even when units are stacked.  A large digital display provides a clear view of the current and set values. 

HRSH Air-cooled recirculating chillers offer a cooling capacity range of 10.5 to 28 kW. Coolant and refrigeration circuits are included in a compact and lightweight package. Extracted heat is air cooled. An inverter provides demand-based rotation control for the compressor, pump and fan, offering substantial energy savings. Electric options ensure global power supply compatibility. Additional

Configure Options...

CAD Downloads

CAD FILES FROM ETECH

View CAD Models

View 3D Model

Product Catalog

Series Catalog

RoHS Certificate

Download Certificate

Power supply 20 3-phase 200 VAC (50 Hz) 3-phase 200 to 230 VAC (60 Hz) Specications Model HRSH100-Al-20-l HRSH150-Al-20-l HRSH200-Al-20-l HRSH250-Al-20-l HRSH300-Al-20-l Cooling method Air-cooled refrigeration Refrigerant R410A (HFC) Refrigerant charge kg 1.27 2.1 2.1 2.8 2.8 Control method PID control Ambient temperature/Altitude Note 1), 9) C Temperature: 20 to 45, Altitude: less than 3000

Lifting height [m] Pressure [MPa] Lifting height [m] Circulating fluid flow rate [LPM] Circulating fluid flow rate [LPM] Required Facility Water Flow Rate HRS050-A-20 (Single-phase 200 to 230 VAC) 0.5 10 20 10 20 50 HRS012-W, HRS018-W, HRS024-W-20 Outlet 60 [Hz] 0.4 40 Facility water flow rate [L/min] 30 0.3 30 25 Outlet 60 [Hz] HRS024-W-20 20 0.2 20 10 20 HRS018-W15 10 0.1 Return port 10

This is included in the response from the product when there is an error in the received request. 9 NAK(15h) Error content is included in the response when there is an error in the received request. Refer to the table below for exception codes.

) Note 20) Note 20) Note 20) Note 20) Note 20) Note 20) Note 15) The combination of metal bowl: 2 and 8 is not available.

HRSH100-A-20/40. 8-13 8.4.2 HRSH150-A-20/40. 8-13 8.4.3 HRSH200-A-20/40. 8-14 8.4.4 HRSH250-A-20/40. 8-14 8.4.5 HRSH300-A-20/40. 8-15 8.4.6 HRSH100-W-20/40. 8-16 8.4.7 HRSH150-W-20/40. 8-16 8.4.8 HRSH200-W-20/40. 8-17 8.4.9 HRSH250-W-20/40. 8-17 8.5 Pump Capacity . 8-18 8.5.1 HRSH100-A-20/40-, HRSH100-W-20/40. 8-18 8.5.2 HRSH150/200-A-20/40-HRSH150/200/250-W-20/40. 8-18 8.5.3 HRSH250/300

Applicable model -A -W HRSH100--20-S HRSH150--20-S HRSH200--20-S HRSH250--20-S HRSH300-A-20-S HEB HED HEA IDH 179 HRSH Series Optional Accessories q Piping Conversion Fitting This is a fitting to change the port from Rc to G or NPT.

Power supply output VI: 20 [kVA] Q = P = V x I x Power factor In this example, using a power factor of 0.85: = 20 [kVA] x 0.85 = 17 [kW] Cooling capacity = Considering a safety factor of 20%, 17 [kW] x 1.2 = W Efficiency Q = P = In this example, using an efficiency of 0.7: 13 0.7 = = 18.6 [kW] Cooling capacity = Considering a safety factor of 20%, 18.6 [kW] x 1.2 = 22.3 [kW] 20.4 [kW] *1

-W-20, OTHERS, HRS THERMO-CHILLERS, 21, HRS - NO SIZE RATING, 2.23666 lb