HRS high capacity standard chillers offer cooling capacities of 9.5, 14.5 and 20.5 kW. Coolant and refrigeration circuits are included in a compact package. The refrigeration circuit is air cooled by a single large fan, with a low sound level of 70~75 dB(A) depending on capacity. Alternately, facility water cooled versions are also available. Set temperatures are PID
temperature [C] [60 Hz] 0 10 20 30 40 50 Circulating fluid temperature [C] HRS050-A-20 8000 7000 6000 5000 4000 3000 2000 1000 00 10 20 30 40 50 Circulating fluid temperature [C] 8000 7000 6000 5000 4000 3000 2000 1000 00 10 20 30 40 50 Circulating fluid temperature [C] Cooling capacity [W] Cooling capacity [W] 25C 25C 32C 32C Ambient Ambient temperature temperature 40C 40C [50 Hz] [60 Hz
HRS100/150 Series 4.10 Register Map 4-17 HRX-OM-S010 Chapter 4 MODBUS communication function 4.10.5 Status flag The status of the product is read by the following assignment.
Your search for HRS returned 21 result(s)
There were no hits with the full part number, but there were 12 hits in the keyword search.
There were no hits with the full part number, but there were 10 hits in the keyword search.
Product Information » New Products Search Results
Cooling Capacity: 100 (10 kW), Cooling Method: A (Air-cooled), Pipe Thread: F (G, w/Rc-G Conversion Fitting), Power Supply: 40 [3-phase 380 to 415 VAC (50/60 Hz)], Option: A (w/Caster Adjuster-foot)
Cooling Capacity: 10 kW, Cooling Method: Air-cooled, Pipe Thread: G, w/Rc-G Conversion Fitting, Power Supply: 40 [3-phase 380 to 415 VAC (50/60 Hz)], Option: w/Caster Adjuster-foot
Thermo-chiller HRS offers convenient functions, self diagnosis and check display for easy maintenance. An angled supply port facilitates the supply of circulating fluid, even when units are stacked. A large digital display provides a clear view of the current and set values. The dustproof filter is integrated with the grill of the front panel allowing mounting and removal of the HRS filter
VM SUP blocking disk assembly SY30M-40-2A SY50M-40-1A SY70M-40-1A EXH blocking disk assembly Series SY3000 SY5000 SY7000 SY30M-40-1A SY50M-40-1A SY70M-40-1A XT34 Label for blocking disk If the blocking disk assembly is ordered using the manifold specification sheet and ordered at the same time as the manifold, the position where the blocking disk assembly is inserted will be labeled and
Cable size Crimped terminal on the rated current thermo-chiller side HRS100-Al-20-l HRS100-Wl-20-l 3-phase 200 VAC (50 Hz) 3-phase 200 to 230 VAC (60 Hz) 4 cores x 5.5 mm2 (4 cores x AWG10) (Including grounding cable R5.5-5) R5.5-5 30 A M5 HRS150-Al-20-l HRS150-Wl-20-l 40 A 4 cores x 8 mm2 (4 cores x AWG8) (Including grounding cable R8-5) R8-5 A HRS100-Al-40-l HRS100-Wl-40-l 3-phase 380 to
/150-A-20. 8-1 8.1.2 HRS100/150-A-40. 8-2 8.1.3 HRS100/150-A-46. 8-3 8.1.4 HRS100/150-W-20. 8-4 8.1.5 HRS100/150-W-40. 8-5 8.1.6 HRS100/150-W-46. 8-6 8.1.7 Refrigerant with GWP reference . 8-7 8.1.8 Communication specification . 8-7 8.2 Outline dimensions . 8-8 8.2.1 HRS100/150-A-20/40/46. 8-8 8.2.2 HRS100/150-W-20/40/46. 8-9 8.3 Flow diagram . 8-10 8.3.1 HRS100/150-A-20/40/46. 8-10 8.3.2
]) (Grommet with membrane) 4.5 [115] 7.0 [179] 4.5 [116] 4.3 [109] Power terminal 7.6 [192] 8.9 [225] Pump drain port Rc1/4 (Valve stopper) 10.7 [272] 20.0 [508] Power cable entry (Hole 1.6 [40]) (Grommet with membrane) 22.9 [583] 13 Series HRS100/150 Thermo-chiller Standard Type Dimensions inch [mm] HRS100/150-W-20 (Water-cooled 200 V type) HRS100/150-W-40 (Water-cooled 400 V type) Anchor
[C] Correction factor 2 to 25 1.14 30 1.04 32 1 35 0.96 40 0.9 Ambient temp. [C] Correction factor 2 to 25 1.06 30 1.02 32 1 35 0.99 40 0.98 45 0.92 Ambient temp. [C] Correction factor 2 to 25 1.10 30 1.05 32 1 35 0.95 40 0.90 Ambient temp. [C] Correction factor 2 to 25 1.2 30 1.04 32 1 35 0.93 40 0.84 Ambient temp.