The JXC*F single axis controller operates LE's 24VDC step motors with incremental or absolute encoders. The Safe Stop 1 (SS1-t) and Safety Torque Off (STO) sub-functions are included. Actuator motors can be operated by calling a line of step data or by direct numerical instruction, each possible via the IO-Link protocol. Further compatible functions include return to origin, alarm outputs
Similar items in stock.
T4 = 0.05 [s] T1 = V/a1 = 300/5000 = 0.06 [s], T3 = V/a2 = 300/5000 = 0.06 [s] T2 = = = 0.94 [s] L 0.5 V (T1 + T3) V 300 0.5 300 (0.06 + 0.06) 300 T4 = 0.05 [s] Therefore, the cycle time can be obtained as follows.
T1 = V/a1 = 300/5000 = 0.06 [s], T3 = V/a2 = 300/5000 = 0.06 [s] 300 0.5300(0.06 + 0.06) 300 T2 = = = 0.94 [s] L 0.5V(T1 + T3) V T4 = 0.05 [s] Therefore, the cycle time can be obtained as follows.
30 50 100 150 200 250 300 350 400 30 50 100 150 200 250 300 350 400 450 500 (kg) 0.580.62 0.73 0.87 0.98 1.09 1.20 1.181.25 1.42 1.68 1.86 2.03 2.21 2.382.56 2.09 2.20 2.49 2.77 3.17 3.46 3.74 4.03 4.32 4.60 4.89 LEY 16 D LEY 25 D LEY 32 D [mm] 1) 30 50 100 150 200 250 300 30 50 100 150 200 250 300 350 400 30 50 100 150 200 250 300 350 400 450 500 (kg) 0.580.62 0.73 0.87 0.98 1.09 1.20
[Setting example] Axis Actuator Lead Electronic gear ratio Axis 1 LEY16C 300 2.5mm 1 / 1 Undefined No.12 1 to 4096 X Axis 2 LEY16B-300 5mm 1 / 2 Axis 3 LEY16A-300 10mm 1 / 4 Adjust the electronic gear ratio in order to travel the same distance per pulse of the axis with the shortest lead (Axis 1).