The ISE70G pressure sensors provide continuous quantitative values, as well as switched digital outputs when pressure set points are met. Compatible fluids include any non-corrosive liquid or gas. 6 pressure ranges are offered up to 50 MPa. This sensor is also IO-Link compatible. Sensor information, such as identity, functional state, cable connection, and current or switch values can be
No.PS-OMV0009-E PRODUCT NAME High-precision Digital Pressure Switch MODEL / Series / Product Number ISE70G-#-L2 ISE75G-#-L2 ISE76G-#-L2 ISE77G-#-L2 ISE78G-#-L2 Table of Contents Safety Instructions 2 Model Indication and How to Order 9 Summary of Product parts 10 Definition and terminology 12 Mounting and Installation 15 Installation 15 Piping 17 Wiring 19 Outline of Settings [Measurement
Similar items in stock.
Input Data2 byteOutput Data0 byte (IO-Link ) ID 131(0x0083) ISE70G-*-L2-*309(0x0135) ISE75G-*-L2-*320(0x0140) ISE76G-*-L2-*321(0x0141) ISE77G-*-L2-*322(0x0142) ID ISE78G-*-L2-*362(0x016A) 1(0 ms) 2 3 ISE70G/ISE75G MPa/kPa ISE76G/ISE77G/ISE78G MPa 490 5https://www.smcworld.com 6 02 N02 F02 Rc1/4 NPT1/4 G1/4 Al2O3(96) ISE70GC3604()FKM+ ISE75G/ISE76G/ISE77G/ISE78GC3604()FKM ISE70G 179 g
M L2 Pressure range Piping specification Symbol Description ISE70G 0 to 1 MPa ISE75G 0 to 2 MPa ISE76G 0 to 5 MPa ISE77G 0 to 10 MPa Symbol Description 02 Rc1/4 N02 NPT1/4 F02 G1/4*1 Option 3 Symbol Description Nil Operation manual Y None *1 ISO 1179-1 compliant Orifice K Operation manual + Calibration certificate Symbol Description Nil None T Yes*1 T Calibration certificate *1 Orifice
VM230U-02-08A VM-08A 110 g Red VM220-02-30RA VM230-02-30RA VM220U-02-30RA VM230U-02-30RA VM-30AR 58 g Black VM220-02-30BA VM230-02-30BA VM220U-02-30BA VM230U-02-30BA VM-30AB Green VM220-02-30GA VM230-02-30GA VM220U-02-30GA VM230U-02-30GA VM-30AG Yellow VM220-02-30YA VM230-02-30YA VM220U-02-30YA VM230U-02-30YA VM-30AY Push button (Mushroom) Red VM220-02-32RA VM230-02-32RA VM220U-02-32RA VM230U