The ISE70G pressure sensors provide continuous quantitative values, as well as switched digital outputs when pressure set points are met. Compatible fluids include any non-corrosive liquid or gas. 6 pressure ranges are offered up to 50 MPa. This sensor is also IO-Link compatible. Sensor information, such as identity, functional state, cable connection, and current or switch values can be
Description Nil None 1 ISO 1179-1 compliant A Bracket A (Interchangeable with ISE70) Output specification1 Symbol Description B Bracket B L2 IO-Link: Switch output 1 + Switch output 2 (Switch output: NPN or PNP switching type) Option 1 1 Refer to pages 7 and 10 for details.
A large bore cylinder or ejector consumes a large amount of air in operation and may experience a temporary drop in the primary pressure. This function prevents detection of such temporary drops in primary pressure as abnormal pressure.
Bracket A (Part No.: ZS-50-A) Bracket B (Part No.: ZS-50-B) -14No.PS-OMV0004-H Piping Piping specification: -02 and -N02 After hand tightening, tighten the fitting using a spanner on the flat surfaces of the fitting. The tightening torque must be 8 to 12 Nm. Piping specification: -F02 After hand tightening, tighten the fitting using a spanner on the flat surfaces of the fitting.