The HRSE recirculating chiller is a basic version of HRS featuring air cooled refrigerant and omitting the heating function. Three cooling capacities are available. The operator interface includes an easy-fill fluid tank with level check, intuitive keypad and digital display, and tool free filter removal. This model is compatible with single phase 100 VAC 50/60Hz power.
HRS012-A-10 HRS012-W-10 HRS018-A-10 HRS018-W-10 Model Air-cooled refrigeration Water-cooled refrigeration Air-cooled refrigeration Water-cooled refrigeration Cooling method Refrigerant Control method Ambient temperature/humidity Note 2) R407C (HFC) PID control Temperature: 5 to 40C, Humidity: 30 to 70% Clear water, 15% ethylene glycol aqueous solution Note 5) Circulating fluid Note 3) Circulating
Power supply Circuit protector (A) 10 10 4.7/5.2 0.9/1.0 20 20 8/11 1.7/2.2 65/68 Applicable earth leakage breaker capacity Note 9) (A) Rated operating current (50/60 Hz) (A) 4.6/5.1 0.9/1.0 5.1/5.9 1.0/1.2 Rated power consumption Note 4) (50/60 Hz) (kVA) Noise level Note 10) (50/60 Hz) (dB) 60/61 Fitting (for drain outlet) 1 pc.
-A-10, HRSE018-A-10) 8.5.2 HRSE012/018/024-A-20/23 0.14 14 0.12 12 Circulating fluid pressure [MPa] Outlet : 60Hz 10 0.10 Pump head [m] 8 0.08 Outlet : 50Hz 0.06 6 0.04 4 Available area Return port 0.02 2 0.00 0 2 4 6 8 10 12 14 16 Circulating fluid flow [L/min] Fig. 8.5-2 Pump capacity (HRSE012-A-20/23, HRSE018-A-20/23, HRSE024-A-20/23) HRSE Series Product Warranty 8-9 HRX-OM-R039 Chapter