The HRR is a temperature control device mountable in a 19-inch rack. Rack mounting recovers desktop or floor space, permitting stacking of related devices and mobility, depending on the rack style. Recirculating fluid removes heat from the process source, which is then removed from the fluid by an air cooled refrigeration circuit. Air cooling frees the installation from dependence on facility
HRX-OM-W004-H Operation Manual Communication function Thermo-chiller Air-Cooled Water-Cooled refrigerated type refrigerated type HRR010-A-10HRR012-A-10HRR018-A-10HRR010-A-20HRR012-A-20HRR018-A-20HRR024-A-20HRR030-A-20HRR050-A-20HRR050-A-40HRR010-W-10HRR012-W-10HRR018-W-10HRR010-W-20HRR012-W-20HRR018-W-20HRR024-W-20HRR030-W-20HRR050-W-20HRR050-W-40Keep this manual available whenever necessary
capacity . 9-11 9.4.1 HRR050-A-20. 9-11 9.4.2 HRR050-W-20. 9-11 9.4.3 HRR050-A-40. 9-12 9.4.4 HRR050-W-40. 9-12 9.5 Heating capacity . 9-13 9.5.1 HRR050-A/W-20. 9-13 9.5.2 HRR050-A/W-40. 9-13 9.6 Pump capacity. 9-14 9.6.1 HRR050-A/W-20. 9-14 9.6.2 HRR050-A/W-40. 9-14 9.7 Required facility water flow (for water-cooled type) . 9-15 9.7.1 HRR050-W-20. 9-15 9.7.2 HRR050-W-40. 9-15 9.8 Types
Required ventilation rate [m3/min] Model Heat radiation amount [kW] Differential temp. of 3C between inside Differential temp. of 6C between inside and outside of installation area HRR010-A Approx. 2 40 20 HRR012-A Approx. 2 40 20 HRR018-A Approx. 4 70 40 HRR024-A Approx. 5 90 50 HRR030-A Approx. 6 100 60 HRR050-A Approx. 10 140 70 and outside of installation area Voltage dV dt = Voltage
Cooling Capacity: 050 [5500/5900 W (50/60 Hz)], Pipe Thread: N [NPT (w/Rc-NPT Conversion Fitting Set)], DI Water Piping: M (Applicable to DI Water Piping), High Pressure Pump: T1 (Inverter Pump Mounted)