The HRR-W is a temperature control device mountable in a 19-inch rack. Rack mounting recovers desktop or floor space, permitting stacking of related devices and mobility, depending on the rack style. Recirculating fluid removes heat from the process source, which is then removed from the fluid by a water-cooled refrigeration circuit. Coolant temperature stability is ±0.1°C within a set temperature
. 9-11 9.4.1 HRR012-A/W-10/20. 9-11 HRR Series HRX-OM-W002 Contents 9.4.2 HRR018-A/W-10/20. 9-11 9.4.3 HRR024-A/W-20. 9-12 9.4.4 HRR030-A/W-20. 9-12 9.5 Heating capacity . 9-13 9.5.1 HRR012-A/W-10-,HRR018-A/W-10-. 9-13 9.5.2 HRR012-A/W-20,HRR018-A/W-20 . 9-13 9.5.3 HRR024-A/W-20,HRR030-A/W-20 . 9-13 9.6 Pump capacity. 9-14 9.6.1 HRR012/018/024/030-A/W. 9-14 9.6.2 HRR012/018-A/W-10-T/MT .
024 030 HRR -W HRR010-W-20 30 20 Facility water flow rate [L/min] Facility water flow rate [L/min] HRR030-W 25 15 HRR024-W 20 15 10 10 HRR018-W 5 5 HRR012-W 0 0 0 10 20 30 40 0 10 20 30 40 50 Facility water inlet temperature [C] Facility water inlet temperature [C] * This is the required facility water flow rate at the circulating fluid rated flow and the cooling capacity listed in the
Cooling Capacity: 018 [1600/1800, (50/60 Hz)], Cooling Method: A (Air-cooled), Pipe Thread: Rc, Option: T1U (T1+U))
Cooling Capacity: 010 [950/1100, (50/60 Hz)], Cooling Method: A (Air-cooled), Pipe Thread: N [NPT (w/Rc-NPT Conversion Fitting Set)], Option: T1U (T1+U))
Cooling Capacity: 010 [950/1100, (50/60 Hz)], Cooling Method: A (Air-cooled), Pipe Thread: F [G (w/Rc-G Conversion Fitting Set)], Option: T1U (T1+U))