The HRR is a temperature control device mountable in a 19-inch rack. Rack mounting recovers desktop or floor space, permitting stacking of related devices and mobility, depending on the rack style. Recirculating fluid removes heat from the process source, which is then removed from the fluid by an air cooled refrigeration circuit. Air cooling frees the installation from dependence
3.10.1 LRC(ASCII) .3-10 3.10.2 CRC(RTU) .3-10 3.11 Explanation of function codes . 3-12 3.11.1 Function code04 Reading multiple registers .3-12 3.11.2 Function code06 Writing registers .3-13 3.11.3 Function code16 Writing multiple registers .3-14 HRR Series HRX-OM-W004 Contents 3.11.4 Function code23 Reading/writing multiple registers . 3-15 3.12 Negative response . 3-16 3.13 Register Map
For HRR012/018/024/030-AF-10/20G thread adapter set 1 set For HRR012/018/024/030-AN-10/20NPT thread adapter set 1 set 1 In the case of option Z, not included.
For HRR010-AF-10/20G thread adapter set 1 set (5) For HRR010-AN-10/20NPT thread adapter set 1 set 1 In the case of option Z, not included.
Applicable model HRR012/018--10-T/MT*1 HRR012/018/024/030--20-T HRR012/018/024/030--20-MT1 Pump Rated flow (50/60 Hz)2, 3 L/min 7 (0.36 MPa)/10 (0.42 MPa) 10 (0.42 MPa)/14 (0.40 MPa) 10 (0.32 MPa)/14 (0.32 MPa) Maximum pump head (50/60 Hz) m 50 50 50 Output W 350 550 Circuit protector A 15 15 (10 A for standard) Recommended earth leakage breaker capacity A 15 Cooling capacity4 W The cooling